Features: • Robust zinc die cast head assembly with glass fiber reinforced plastic or zinc die cast body • Three solenoids voltages: 24Vac/dc, 120Vac and 240Vac • Power-to-lock or power-to-unlock types for key trap (2500N holding force) • Flexible switching arrangement • 24 V, 110 Vac, and 230 Vac coil voltages • Override mechanism in cover • Head may be rotated into 4 different positions • Three conduit openings (knock-out style) • Switch position provides status • Choice of different contact blocks • Indicators for switch and solenoid status (optional) • Positive Opening of NC contacts • Cable entry available: M20, and 1/2"NPT • Approval: CE, cULus (pending) | Installation dimensions |
Specifications: Rated thermal current (Ith) 5 A Sealing:SSD6191 IP65; NEMA 1, 4, 12, 13/SS6191 NEMA 1,4,6,12,13 Rated impulse withstand (Uimp) :2500 V Pollution degree: 3 (macro-environment, installation environment) Rated insulation voltage :(Ui) 600 V Operating temperature range: -25 °C to 50 °C [-13 °F to 122 °F] Storage temperature range: -40 °C to 85 °C [-40 °F to 185 °F] Short-circuit protective device (type/maximum rating): Class J fuse (10A/600 Vac) Expected mechanical life : 1,000,000 operations Conditional short-circuit current :1000 A Solenoid operating voltage and power : 24 Vac: +10 %, -15 %, 4 W 110 Vac: +10 %, -15 %, 8 W 230 Vac: +10 %, -15 %, 9 W 24 Vdc: +10 %, -20 %, 7 W |